A pressure gauge may be a simple local indicator or a critical diagnostic instrument. Correct selection helps operators read the process while protecting the instrument from temperature, vibration, pulsation, corrosion and overpressure. Use the complete application, not just the maximum number on the dial.
1. Identify the pressure type
- Gauge pressure: relative to atmosphere, common in pumps, compressed air and hydraulics.
- Absolute pressure: relative to vacuum, used where atmospheric variation must not influence the reading.
- Differential pressure: the difference between two points, used for filter monitoring, flow, vessel level and clean-room pressure.
- Vacuum or compound: for processes below atmosphere or crossing between vacuum and positive pressure.
2. Select a useful range
Normal pressure should sit in a readable part of the scale with room for expected variation. A gauge operating close to full scale may be vulnerable to spikes, while an excessively broad range hides small changes. Include startup, shutdown and blocked-line conditions.
3. Set accuracy and readability
Choose accuracy for the decision based on the reading. Maintenance indication, process adjustment and calibration reference require different performance. Consider dial diameter, viewing distance and units. Digital gauges can offer high accuracy and communications; mechanical gauges remain practical for many local readings.
4. Match the sensing element
Bourdon-tube gauges suit many common ranges. Diaphragm and capsule elements address different low-pressure, differential and demanding-media duties. Verify that the process connection and any seal system are compatible with the selected element.
5. Check the medium
Identify corrosive, viscous, sanitary, clogging or crystallising characteristics and confirm every wetted material. A diaphragm seal can isolate the gauge from aggressive, hot or easily blocked media, but fill fluid, capillary and temperature effects need engineering review.
6. Account for temperature and vibration
High process temperature can damage the mechanism or change accuracy. Cooling elements, siphons or remote seals may help where suitable. Vibration and pulsation make readings unstable and shorten life; liquid filling or a carefully selected snubber can add damping.
7. Verify installation and safety
Specify thread or flange standard, size, connection position and mounting style. Install the gauge where it can be isolated, depressurised and calibrated. For hazardous media or high stored energy, review safety-pattern construction, blow-out features, solid fronts and window materials.
RFQ checklist
Provide pressure type and range, normal value, accuracy, medium, temperature, ambient conditions, connection, case size, wetted materials, accessories and approvals. Include dial, connection and model-code photographs for replacements.
US2 Automation can assist with identifying pressure gauges, transmitters and switches. Final suitability should be confirmed by a qualified instrumentation engineer.
Technical references
Prepared using WIKA’s public guidance on pressure-gauge selection, pressure gauges and differential-pressure applications.